UL 508A Panel Construction with the Details Documented

ACT Solutions is a UL 508A certified panel shop authorized to build and label qualifying industrial control panels under its UL program.

01 What the label represents

More than a sticker on an enclosure

Our process goes beyond placing a label on an enclosure: we review components, protection, wiring, grounding, enclosure suitability, markings, and required manufacturing records as they apply to the panel.

That review is the part of a UL 508A build that a customer never sees directly, but it is the part that determines whether the panel passes inspection, matches the drawings, and behaves the way the design intended once it is energized in the field.

UL File
E550763
Shop status
UL 508A certified industrial control-panel shop
Location
West Jordan, Utah
Open stainless steel control panel showing the nameplate and warning labels on the inside of the door, a document pocket, door-mounted relays with labeled wiring, and a subpanel with breakers and terminal blocks.
Labeled UL 508A panel with drawing pocket and organized subpanel

02 Review & quality process

What we check, as it applies to your panel

Not every item applies to every panel. These are the checks that make up a UL 508A build in our shop.

Component suitability
Verification that components are suitable for the application and carry the UL status the panel requires.
Short-circuit current rating
SCCR review for the assembly, so the panel is rated for the fault current available where it will be installed.
Overcurrent protection
Review of protective device selection, ratings, and coordination within the panel.
Conductor sizing & wiring methods
Conductor sizing, insulation, routing, and wiring-method checks against the requirements that apply.
Grounding & bonding
Grounding and bonding checks through the enclosure, backplate, and door-mounted equipment.
Enclosure suitability
Confirmation that the enclosure type and rating suit the installed environment.
Markings & labels
Required markings and labels applied and legible, including the panel nameplate.
Torque & continuity verification
Terminations torqued and verified, with continuity checked against the drawings.
Records & traceability
Serial-number assignment and retained manufacturing records for the panels we label.

03 In plain language

What SCCR means for your project

SCCR stands for short-circuit current rating. It is the maximum fault current a panel can safely handle at its supply terminals without becoming a hazard. Every installation has a certain amount of fault current available at the point where the panel connects, and the panel has to be rated at or above that number.

Practically, this means the SCCR is decided by the components you specify and how they are protected — not by the enclosure. If a BOM contains a device that drags the assembly rating below what the site needs, it is much cheaper to find that during quoting than during startup. That review is part of how we quote a UL 508A panel.

If you know the available fault current at the installation, send it with your drawings. If you do not, tell us and we will flag it as an item to confirm.

04 Customer benefit

Why it matters downstream

  • Greater confidence in panel construction and component suitability
  • Clearer requirements for inspectors, contractors, and end users
  • Documented SCCR and required markings
  • Traceability through serial numbers and retained records
  • Fewer avoidable surprises at delivery or installation
How we describe UL status ACT Solutions is a UL 508A certified panel shop. An individual panel is described as a UL 508A listed and labeled panel only when that panel actually qualifies and receives the mark.

05 Existing panels

Customer-supplied panels and UL evaluation

We can review customer-supplied panels and enclosures for UL listing. Whether a label can be applied depends on the enclosure, the components installed, and the wiring methods used — so we look at the panel and the documentation before we commit to an outcome.

See customer-supplied panel capabilities

// Start a project

Ask Us About Your UL 508A Requirements

Tell us what the specification calls for — required listing, available fault current, enclosure rating, or an existing panel that needs evaluation — and we’ll tell you what it takes.